Description
Victron Phoenix 24/3000 – 120 Volt AC 2400 Watt Output Pure Sine Wave Power Inverter – 24 Volt Input
Pure sine wave output, high peak power and high efficiency. Combined high frequency and line frequency technologies ensure the best of both worlds.
SinusMax – Superior engineering
Developed for professional duty, the Phoenix range of inverters is suitable for the widest range of applications. The design criteria have been to produce a true sine wave inverter with optimised efficiency but without compromise in performance. Employing hybrid HF technology, the result is a top quality product with compact dimensions, light in weight and capable of supplying power, problem free, to any load.
Parallel and 3-phase operation capability
Up to 6 Phoenix Inverters can operate in parallel to achieve higher power output. Six 24V 5000VA units, for example, will provide 24kW / 30kVA output power. Operation in 3-phase configuration is also possible.
Victron Phoenix 24/3000 Specifications:
- Parallel, 3-phase And Split-Phase Operation
- Input voltage range (V DC) 19 – 33
- Output Output voltage: 120 VAC ±2% Frequency: 60 Hz ± 0,1% (1)
- Cont. output power at 25ºC / 77ºF (VoltAmps) 3000
- Cont. output power at 25ºC / 77ºF (Watts) 2400
- Cont. output power at 40ºC / 104ºF (Watts) 2200
- Cont. output power at 65ºC / 150ºF (Watts) 1700
- Peak power (Watts) 6000
- Max. efficiency 94%
- Zero load power (Watts) 20
- Zero load power in AES mode (Watts) 15
- Zero load power in Search mode (Watts) 10
- Operating temperature range: -40 to +65ºC (-40 – 150°F)
- Humidity (non-condensing): max 95%
- Battery Connection – 2+2 M8 Bolts
- 120 VAC Connection – Screw Terminals
Additional Features:
- 3 Programmable relays that can a.o. be set for general alarm, DC under voltage or genset start/stop function.
- Output Short Circuit
- Overload Protection
- Battery Voltage Too High
- Battery Voltage Too Low
- Temperature Too High
- input voltage ripple too high
- VE.Bus communication port For parallel and three phase operation, remote monitoring and system integration
- Remote on-off Switch
- Weight 18 kg 38 lbs
- Dimensions 362Hx258Wx218D (mm) 14.3Hx10.2Wx8.6D (inches)
STANDARDS:
- Safety EN 60335-1
- Emission Immunity EN 55014-1 / EN 55014-2
1) Can be adjusted to 60 Hz and to 240 V
2) Non-linear load, crest factor 3:1
3) Programmable relay that can a.o. be set for
general alarm, DC under voltage or genset
start/stop function.
DC rating: 1 A up to 60 VDC
Similar Products: Victron Phoenix 12/3000 120VAC
There are no reviews yet.